Auto Section Switch (Oil/Air) 2019-08-30T03:50:27+00:00

Auto Section Switch (Oil/Air)

Features

Multi-point neutral grounding system. Can make or break malfunctioning areas of power distribution line.
Minimizing the damage to customer facilities.

  • High technic
    Small and light, which makes it easy to use
    Uses Air Puffer-type interruption method, as it uses air insulation
    Fuse attachment, maintenance and repair easy
    CT-type base insulator applied
    Available in a wide range of temperatures -20℃ ~ 40℃
  • Safety
    Safe operation in live wire
    Operation and opening can be viewed by eye – prevents accidents during maintenance/repair
    Excellent arc interruption abilities
  • Easy installation
    Can be installed vertically or horizontally
    Easy operation via flexible type manual cable method
    Small and light, which makes it easy for installation
  • Overload protection
    In over current lock below 800A, it operates under inverse time characteristic.
  • Charged spring trip
    When the product is undergoing breaking operation according to T-C curve due to overloading, or if the backup protection is operating even if ASS wasn’t broken as overload has been removed, zero voltage will occur. Then, ASS will instantaneously release to isolate the line downstream of ASS.
  • Inrush-current blocking function
    When ASS has operated correctly (Current bigger than 10% but smaller than 100% of setting current) and has broken an opening motion and then proceeded to close, this function will stop ASS mistaking the inrush-current from downstream equipment and malfunctioning.
  • Over current locking funtion
    If a malfunction which is bigger than rated interrupting current (900A) occurs, the prouct will product the switch. If the current is biger than the lock current (800A±10%), the switch will lock. GASS will then be interrupted in zero voltage after malfunctioning current is removed by backup protection.
  • Service condition
    Surrounding temperature: maximum 40/Minimum 20℃
    Altitude: less than 1,000m
    Installation method: vertically or horizontally
Inquiry

Ratings(Indoor Type)

Type JW-AISS JW-AISS-FH(LA) JW-AISS-FV(LA)
General Fuse+L/A(slanted) Fuse+L/A(vertical)
Rated voltage 25.8
Rated current 200
Rated power frequency 60
Power frequency withstand voltage (kV/1min) 50
(kV/1min) 50
(kV/1min) 60
Impulse withstand voltage Conductive part and to ground (kV/1min) 125
Mutual two-phase conductive part (kV/1min) 125
Longitudinal (kV/1min) 145
Rated short-time withstand current Short (kA, Asym) 15
1 sec (kA, sym) 10
10 sec (kA, sym) 3.5
Rated short-circuit making current(kA, (Asym) 15
Rated short-circuit breaking current (A) 900
Minimum operating current Phase (A) 10/20/30/50/70/100/140/200/BLOCK
Ground (A) 5/10/15/25/35/50/70/100/BY-PASS
 Maximum over-current lock current(A) 800
Insulating medium Air
 Operating voltage Close DC 24V
Open DC 24V
 Weight (kg) 78kg (General) 97kg (Slanted) 106 kg (Vertical) 3kg (Controller)
Input Voltage (V) AC220V (for Battery charging )
Applied standard KEMC 1126 (2007. 8)

* For additional information, please contact us directly.
* Specifications of this product may be changed without prior notice in order to improve its quality.

Outdoor type – Oil insulation

Type ASO-AJ
 Rated Voltage(kV) 25.8
  Rated Current(A) 200
 Rated power frequency(㎐) 60
Power Frequency withstand Voltage Drying (kV/1min) 60
Wet (kV/10sec) 50
Impulse withstand Voltage(1.2×50μs) (kV) 150
Rated short-time withstand current Short (kA, Asym) 15
1 sec (kA, sym) 10
10 sec (kA, sym) 3.5
Rated short-circuit making current(kA, (Asym)) 15
Rated short-circuit breaking current(A) 900
 Operating voltage(V) DC 24V
Minimum operating current Phase (A) 10/20/30/50/70/100/140/200/BLOCK
Ground (A) 5/10/15/25/35/50/70/100/BY-PASS
 Maximum over-current lock current(A) 800
 Insulating medium Oil
 Weight(kg) 170 kg
Input voltage (V) Built in self-charged device
 Applied standard KEMC 1126 (2007. 8)

* Inquire separately besides what is written above.
* The specifications of this product is subject to change without prior notification for quality improvement.

Operating conditions

Surrounding temperature: Maximum 40/Minimum -25
Altitude: Less than 1000m
Installation: Outdoor

Efficiency / Technical information

Phase & Ground current setting table

Transformer capacity (kVA) Phase current(A) Ground current(A) Calculated phase current(A) Calculated ground current(A)
0-10 10 5 0-7.5 0-3.8
10-250 20 10 7.5-18.75 3.8-9.4
251-350 30 15 18.75-26.25 9.4-13.2
351-600 50 25 26.25-45 13.2-22.5
601-900 70 35 45-68 22.5-34
901-1000 100 50 68-75 34-37.5
1001-1500 140 70 75-113 37.5-56.5
1501-200 200 100 113-150 56.5-75
Remark * BLOCK : Blocking on / off tap by phase current
* BYPASS : Blocking open tap by ground fault

* Ground current= (contract capacity/(√3 x 22.9kV)) x (2~3)
* Ground current is set to 1/2 of phase current.