Surge Arrester 2019-04-15T08:07:56+00:00

Surge Protector

Surge Arrester

Features

◆ Uses silicone, a newly arising novelty polymer material
◆ Excellent pressure relief and airtight structure
◆ Suitable for outdoor and damaged areas
◆ Unchanging surge absorption abilities in long-term uses

If different types of overvoltage such as lightening surge or switching surge occurs in a circuit, it may lead to accidents including voltage breakdown of electric installation such as transformers, motor, circuit breaker, switch or cables, as well as damage of power apparatus. This product limits the overvoltage due to different types or surge and prevents voltage breakdown as well as protecting human lives and equipment from explosion.

  • Has excellent protective insulation as it uses ZnO, which has a high limiting voltage
  • As this is a spindle type arrester, it has adequate response characteristics. It also has guaranteed activity on surge that overlaps.
  • As it uses ZnO, which has a high current impulse withstand, it absorbs surge perfectly despite long-term usage.
  • As this is a Gapless type arrester using ZnO, it is maintenance free.
  • The structure of this product is FRP filament winding, which leads to excellent pressure relief. This means that it is safe from accidents from explosion and scattering (polymer-type)
  • The product is completely airtight. (polymer type)
  • Because it’s made up of silicone, it has less danger of breaking due to external pressure. (polymer type)
  • It uses silicone, which is an excellent water repellent. This makes it suitable for use in damaged areas or outdoors. (polymer type)
Inquiry

Ratings

Porcelain Type

Type SAZ-1825 LAZ-18045 LAZ-18090 LAZ-18180
Ratedl voltage(kV) 18 4.5 9 18
Standard nominal discharge current(kA) 2.5 5
Max. continuous operating voltage(kV) 15.3 3.825 7.65
Reference voltage(V1㎃) (kV) AC 16.20 Over 4.05 Over 8.10 Over 16.20 Over
DC 22.90 Over 5.73 Over 11.46 Over 22.90 Over
Residual voltage(8/20㎲, kV crest) 65 14.5 29 58
Discharge current capacity(4/10㎲) (kA) High current short duration(4/10㎲, kV crest) 25 65
Low current long duration 500 1,000
A crest 50 75
 Applied standard ES 153 IEC 60099-4

Polymer Type

Type JPSA-06 JPSA-12 JPSA-18
Ratedl voltage(kV) 6 12 18
Standard nominal discharge current(kA) 5
 Max. continuous operating voltage(kV) 5.1 10.2 15.3
Reference voltage(V1㎃) (kV) AC 5.40 Over 10.82 Over 16.20 Over
DC 7.63 Over 15.30 Over 22.90 Over
 Residual voltage(8/20㎲, kV crest) 19.3 38.6 58.0
(4/10㎲) (kA) / Discharge current capacity High current short duration(4/10㎲, kV crest) 65
Low current long duration 1,000
A crest 75
Applied standard IEC 60099-4, (ES)